Emerson Liebert GXT-3000MTPLUS230 long backup


The Liebert® GXT MT+ has a comprehensive
specification that provides a higher level of
availability to the IT equipment. It satisfies
safety criteria and electromagnetic
compatibility standards while offering
intelligent monitoring and network
management functions. This high
performance UPS with proven reliability is
available in a compact tower design.
Bringing our Enterprise Level IT Expertise
to your SMB
Vertiv offers a full range of power protection
solutions suitable for every requirement or
scenario. From desktop computing, network
equipment, computer rooms to large scale
data centers, we make sure you get the
same level of protection the Fortune 500
companies enjoy with Vertiv. It is our way of
Bringing Enterprise Level IT expertise to
your SMB.
The Liebert® GXT MT+ features best-in-class power
protection for critical applications with the use of true
on-line double conversion technology.
Desktop Computing
> Liebert® PSP
> Liebert® PSA
> Liebert® itON BX
Network / Computer Room
> Liebert® GXT MT+ H
> Liebert® PSI
> Liebert® GXT3
Data Center
> Liebert® APM
> Liebert® NX
> Liebert® Hipulse

Technical Specifications
System Features
Part Number Standard Model GXT-1000MTPLUS230H GXT-2000MTPLUS230H GXT-3000MTPLUS230H
Capacity (VA/W) 1000 / 800 2000/1600 3000/2400
Input Parameters
Frequency Range 40Hz – 70Hz (50Hz/60Hz auto sensing)
Phase Single phase with ground
Power Factor ≥ 0.99 @ 220 to 230 VAC (input voltage)
Voltage Range
Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC
High Line Transfer 300 VAC ± 5%
Output Parameters
Output Voltage 208/220/230/240VAC
AC Voltage Regulation ± 1% (Batt. Mode)
Frequency Range 47 to 53 Hz or 57 to 63 Hz (Auto Sensing)
Frequency Range (Batt. Mode) 50 Hz ± 0.25Hz
Overload 100% to 110%: audible warning 110% to 130%: UPS shuts down in 30
seconds at battery mode or transfers to bypass mode when the utility
is normal. >130%: UPS shuts down immediately at battery mode or
transfer to bypass mode when the utility is normal.
Current Crest Ratio 3:1
Harmonic Distortion ≤ 3 % THD (Linear Load)
≤ 6 % THD (Non-linear Load)
≤ 4 % THD (Linear Load)
≤ 7 % THD (Non-linear Load)
Waveform (Batt. Mode) Pure Sinewave
Efficiency
AC Mode ~ 85% ~ 88%
Battery Mode ~ 83%
Transfer Time
AC Mode to Batt. Mode Zero
Inverter to Bypass 4 ms (Typical)
Battery Charger (Standard Model)
Battery Type 12 V /7 AH 12 V / 9 AH
Numbers 3 6 6
Typical Recharge Time 4 hours recover to 90% capacity (Typical)
Charging Current 1.0 A(max.)
Charging Voltage 41.0 VDC ± 1% 82.1 VDC ±1%
Battery Charger (Long Back-Up Model)
Number 3 8
Charging Current 4.0 A or 8.0 A(max.)
Charging Voltage 41.0 VDC ± 1% 109.6 VDC ±1%
Physical Parameters
Dimension,
D x W x H
220 x 145 x 397 318 x 190 x 421
Net Weight (kgs) 13 7 26 13 28 13
Environmental Parameters
Operation Humidity 20 to 90 % RH @ 0 to 40°C (non-condensing)
Noise Level Less than 55dBA @ 1 Meter
Agency Approval
Safety IEC/EN 62040-1, CE Mark
EMC Directives IEC/EN 62040-2 (EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11,
EN61000-2-2: 2002, EN61000-3-2, EN61000-3-3)
Management
Smart RS-232 or USB Supports Windows 98/2000/2003/XP/Vista/2008/ 7, Linux, and MAC
Optional SNMP Power management from SNMP manager and web browser

Category:

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “Emerson Liebert GXT-3000MTPLUS230 long backup”